On-Line UPS Double Conversion (High Frequency Type)
|

|
RP-UPH series
Double conversion On-Line UPS High Frequency Type
|
RP-UPH Series On-Line UPS is designed with latest technology, making it distinguished by its performance and reliability. The input range is extraordinary wide from 118V to 300V so that the UPS can still run well in areas of poor utility and be robust in various applications. It also eliminates unnecessary battery discharges to prolong the life expectancy of battery. The rectifier stage of RP-UPH series implements high frequency, PWM and power factor correction method. Therefore, the input current is purely sine wave, and power factor can be over 95%. RP-UPH Series have very small harmonic current drawn from the utility. That is, it generates no interference to the utility. Beside, the inverter of the unit adopts newest and tough IGBT, high frequency PWM method. So it can response quickly to load change, especially the impressing capability of starting computer load. All power stages are carefully designed to optimal efficiency so as to save the user running cost, and minimize heat dissipation. The unit, controlled by the innovative software programs, can self-diagnose all the time and provides various status and data displayed clearly on the panel. |
FEATURES
|
| |
True sine-wave double conversion on-line UPS |
| |
Multiple Microprocessor High frequency design & DSP Technology |
| |
Unity input power factor and wide input range |
| |
Extended backup time |
| |
Communication ports selectable: Smart RS232, SNMP, AS-400, USB and DB-9 |
| |
DC start and automatic self-diagnostic function |
| |
Low heat dissipation in long time operation |
| |
High efficiency design to save electricity |
| |
Enhanced protections against lighting surges, disturbances etc. |
| |
Designed to operate under harsh environment |
| |
6KVA-10KVA support Parallel Redundancy function & Capacity Expansion |
| |
10KVA built in two-step charger to reduce charging time |
|
|
SPECIFICATIONS
|
| Model (LCD Series) |
|
|
|
RP-UPH104T |
| Input |
Capacity |
|
|
|
10KVA/7000W
|
| Phase |
Single Phase
|
| Nominal Voltage |
|
1P2W 220Vac |
| Voltage Range |
|
176-276Vac 3Vac |
| Frequency |
50Hz / 60Hz 4Hz
|
| Power Factor |
|
|
0.98
|
| Output |
Voltage |
|
220VAC 1% (230V or 240V re-settable via LCD panel) |
| Frequency |
Synchronized ( Line mode); 50Hz or 60Hz +/-0.5% (Battery mode) |
| Wave-form |
True Sine wave
|
| Distortion |
Tower |
|
|
4% (linear load) 7% non-linear load)
|
| Overload Capacity |
|
105%~130% :10 min., >130% : 1min |
| Crest Ratio |
3:1
|
| Battery |
DC Voltage |
|
|
240V
|
| Capacity |
|
|
|
12V / 7Ah X 20 pcs
|
| Back-up Time |
|
|
|
>5min.
|
| Charger |
Built-In /Option |
|
|
2Amp/4.2Amp (steps)
|
| Recharging Time |
|
|
8 hrs to 90%
|
| Indicator |
LCD (Series) |
UPS status, I/P&O/P Voltage & Frequency ,Load %, Battery Voltage, Battery Capacity % ,Temperature, Model Spec., Event Log. LED: Normal (Green), Warning (Yellow), Fault (Red)
|
| LCD (Series) |
Normal (Green), Bypass(Yellow), Battery Low (Yellow), Inverter (Green), Load% (5 LEDs), Battery % (5 LEDs), Fault (Red)
|
| Outlet |
Tower |
|
|
Terminal Blocks
|
Audible Alarm
|
Battery Mode |
Beeping every 4 seconds (re-settable)
|
| Battery Low |
Beeping every seconds
|
| Overload |
Beeping twice per second
|
| Fault |
Beeping Continuously
|
| Interface |
RS-232 Interface |
UPSilon2000 monitoring software for Windows all, Unix systems and Novell.
|
| Multi-Interface Slot |
SNMP card, AS 400, Dry Contact, USB Selectable
|
| Network |
Surge Protection |
|
N/A
|
| Parallel |
|
Available(Option)
|
| Environment |
Temperature |
0C~40C; 32~104F
|
| Humidity |
0%-95% Non-Condensing
|
| Acoustic Noise |
|
|
<55 dBA (at 1M)
|
| Physical |
Weight (w/o Battery) |
|
|
|
38kgs
|
| Weight (w/Battery) |
|
|
|
93kgs
|
Dimension W*H*D |
|
|