MODEL
|
|
|
RP-3003A
|
|
Capacity
|
|
|
3KVA / 2100W
|
|
Input
|
Voltage |
110/115/120VAC or 220/230/240VAC
|
|
86VAC~144VAC or 172VAC ~288VAC (+ 25%)
|
| Frequency |
47Hz~53Hz or 57Hz~63Hz
|
|
Output
|
Voltage Regulation (Batt. Mode)
|
110/115/120VAC or 220/230/240VAC +/-10%
|
| Frequency |
50Hz or 60Hz +/-1Hz
|
| Waveform |
Simulated Sinewave
|
| Transfer Time |
< 6ms (Typical)
|
IEC-320:Battery/ Surge onl |
|
9/0
|
NEMA 5-15R:Battery/ Surge only |
|
6/0
|
|
Efficiency
|
To AC mode
|
|
86%
|
|
To Battery mode
|
|
83%
|
|
Battery
|
Battery Type |
|
12V/9AH*4pcs
|
Recharge Time
|
5Hrs to 90% after complete discharge
|
| User Replacement |
Yes
|
| Battery Protection |
Over discharge protection & Short circuit protection by fuse
|
| Advanced Battery Management |
Yes
|
Battery Back-up Time |
It depends on connecting loads and external battery packs
|
|
Function
|
Display(LCD)
|
LCD display for AC normal,Back up,AVR protection,Load and Battery level, Overload and UPS cut off
|
| Alarm |
Buzzer on for Back-up mode,Battery low,Overload
|
Output Short Protection |
AC fuse and Electronic circuit (Line mode): Eletronic circuit (Back-up mode)
|
| Communcation Port(RS-232) |
Shutdown Software for Windows 95/98/NT/2000/ME/XP/Vista
|
Modem/Phone Protection |
RJ-11/RJ-45
|
Lightning/Surge Protection
|
240joules
|
AVR (Auto. Voltage Regulation)
|
Boost/Buck
|
| DC Start Function |
Yes
|
| Auto. Restart UPS |
Yes
|
| Over/Under Voltage Protection |
Yes
|
|
Environment
|
Safety Standard |
CE (EN50091-1,EN62040-1-1)
|
EMC Standard
|
UPS status, I/P & O/P Voltage & Frequency, Load %, Battery voltage & % Model Spec.
|
| Operating Temperature |
| Relative Humidity |
| Audible Noise |
|
Physical
|
Dimension(D*W*H) |
|
310 * 440 * 132mm(3U)
|
| Net Weight |
|
27.5Kgs
|