| General |
| Topology |
Line interactive |
| Configuration |
Rack/Tower |
| Part Number |
PW5130i3000-XL3UAU |
| Color |
Black |
| Rating (VA/Watts) |
3000/2700 |
| Diagnostics |
Full system self-test at power up |
| Efficiency |
Normal or line mode: >94% |
| Dimensions (H x W x D, mm) |
131 x 441 x 484 |
| Weight (kg) |
34.3 |
| Rail Kit Included |
Rail kit/tower stand included with all units |
| Remote Emergency Power off (REPO) |
Rear deck emergency stop connector (for remote on/off and power off) |
| |
| Electrical Input |
| Connection |
(1) IEC-320-C20
|
| Nominal Voltage |
230 VAC |
| Voltage Range |
160-294V |
| Frequency |
50/60 Hz |
| Frequency Range |
47-70 Hz for 50 Hz operation 56.5-70 Hz for 60 Hz operation |
| Breaker Ratings |
16A |
| |
| Electrical Output |
| Output Receptacles |
(8) IEC-320-C13
(1) IEC-320-C19
|
| Over Current Protection |
Electronic current limit |
| On Utility Voltage Regulation |
184-265 Vac |
| On Battery Voltage Regulation |
-10%, +6% of nominal |
| Transfer Time |
14 ms typical |
| Load Crest Factor |
3:1 |
| Load Segments |
Two groups of two individually controlled output receptacles |
| |
| Battery |
Runtime (minutes)
Load (watts)
0
100
200
300
400
500
600
700
800
900
1000
1100
1200
|
|
Standard runtime |
|
|
with 1 ebm |
|
|
with 2 ebms |
|
|
with 3 ebms |
|
|
with 4 ebms |
Battery runtimes are approximate and may vary with equipment, configuration, battery age, temperature, etc.
|
| Battery Replacement |
Hot-swappable internal batteries |
| Start On Battery |
Allows start of UPS without utility input |
| |
| Communications |
| LEDs |
13 status-indicating LEDs |
| Communication Ports |
Serial Port RS-232 (RJ45) ports; USB Port As standard (HID). RS-232 and USB 6-ft communication cables included |
| Communications Card Slots |
Optional ConnectUPS-MS Network Management Card, Relay/Serial Management Card -MS |
| Power Management Software |
Eaton Software Suite CD-ROM (bundled with UPS) |
| |
| Environmental & Standards |
| Heat Dissipation (BTU) |
Line: 588 Bat: 3071 |
| Audible Noise |
Max 45 dBA |
| Operating Temperature |
0C to +40C |
| Safety markings |
CE; C-Tick; TUVus |
| EMC Markings |
IEC/EN 62040-2 EN 50091-2 class B, C-Tick |
| Approvals |
IEC/EN 62040-1-1, UL 1778 |
| Storage Temperature |
-15C to +50C |
| Relative Humidity |
2095% non-condensing |