| General |
| Topology |
Online (Double Conversion) |
| Configuration |
Rackmount |
| Part Number |
PW9130G2000R-XL2UAU |
| Color |
Black |
| Rating (VA/Watts) |
2000/1800 |
| Diagnostics |
Full system self-test |
| Efficiency |
94% in high-efficiency mode; 90% in online mode |
| UPS Bypass |
Automatic bypass |
| Dimensions (H x W x D, mm) |
86.5 x 438 x 600 |
| Weight (kg) |
29 |
| Rail Kit Included |
Yes |
| Remote Emergency Power off (REPO) |
Emergency shutdown control through the REPO port |
| |
| Electrical Input |
| Connection |
(1) IEC-320-C14
|
| Input Cord |
Aust. 10A to IEC 320-10A |
| Input Voltage Range |
180-276 Vac (with load PF of 0.7) |
| Nominal Voltage |
220-240 V |
| Frequency |
50/60 Hz |
| Frequency Range |
4565 Hz |
| Nominal Current |
8.7A @230V |
| Breaker Ratings |
10A |
| |
| Electrical Output |
| Output Receptacles |
(4) IEC-320-C13
(4) Aust. 10A
|
| On Utility Voltage Regulation |
3% of nominal |
| On Battery Voltage Regulation |
3% of nominal |
| Frequency Regulation |
3% Hz online |
| Load Crest Factor |
3 to 1 |
| |
| Battery |
Runtime (minutes)
Load (watts)
200
400
600
800
1000
1200
1400
0
500
1000
1500
2000
2500
3000
3500
4000
4500
5000
|
|
Standard runtime |
|
|
with 1 ebm |
|
|
with 2 ebms |
|
|
with 3 ebms |
|
|
with 4 ebms |
Battery runtimes are approximate and may vary with equipment, configuration, battery age, temperature, etc.
|
| Battery Description |
VRLA 12V/9 Ah (internal and External) |
| Battery Type |
Replaceable maintenance free sealed lead acid |
| Battery Replacement |
Hot-swappable internal batteries |
| Start On Battery |
Allows start of UPS without utility input |
| |
| Communications |
| User Interface |
Graphical LCD with blue backlight and text in English, French, German, Russian and Spanish |
| LEDs |
Four status-indicating LEDs |
| Communication Ports |
RS-232 and USB HID port as standard |
| Relay Output |
Common alarm standard |
| Communications Slot |
Optional communication slots (BD Slot) |
| Communications Card Slots |
Optional SNMP/Web card for monitoring in SNMP-based networks, monitoring through Web browser interface. Relay card for integration to industrial environment and BMS, remote shutdown for IBM AS/400 systems |
| |
| Environmental & Standards |
| Heat Dissipation (BTU) |
Line: 838, Bat: 1348 |
| Audible Noise |
<44 dB |
| Operating Temperature |
0C to +40C |
| Performance - Safety - EMC |
CE (per IEC/EN62040-2: Emissions, Category C1; Immunity, Category C2), GS |
| Storage Temperature |
-20C to +40C with batteries and -25C to +55C without batteries |
| Relative Humidity |
590% non-condensing |