General |
|
|
Topology |
On-line
double conversion with PFC (Power Factor Correction)
system |
|
Configuration |
Tower |
|
Part
Number |
9SX6KI-AU |
|
Rating
(VA/Watts) |
6000/5400 |
|
Dimensions
(H x W x D, mm) |
575
x 244 x 542 |
|
Weight
(kg) |
65.5 |
|
Warranty |
2
years |
|
Electrical
Input |
|
|
Connection |
Hardwired
- see manual for terminal block layout |
|
Input
Voltage Range |
180-276V
without derating (up to 120–276V with derating) |
|
Nominal
Voltage |
200/208/220/230/240V |
|
Frequency |
50/60
Hz autoselection |
|
Frequency
Range |
40-70
Hz |
|
Short
Circuit Current |
90
A |
|
Electrical
Output |
|
|
Voltages |
200/208/220/230/240V
+/– 2% |
|
Voltage
THD |
<
3% |
|
Output
Receptacles |
Hardwired
- see manual for terminal block layout |
|
Overload
Capacity |
102–110%
: 120s, 110–125%: 60s, 125–150%: 10s, >150%: 500ms |
|
Efficiency
(Normal Mode) |
Up
to 94% in Online mode, 98% in Hi-Efficiency mode |
|
Output
Frequency |
50/60
Hz autoselect, frequency converter as standard |
|
Load
Crest Factor |
3:01 |
|
Battery |
|
|
Battery
Management |
ABM®
and Temperature compensated charging method (user selectable), automatic
battery test, deep discharge protection, automatic recognition of external
battery units. |
|
Extended
Battery Capability |
EBM |
|
Communications |
|
|
User
Interface |
Multilingual
graphical LCD display |
|
Communication
Ports |
1
USB port + 1 serial RS232 port + 1 mini-terminal block for Remote Power
Off + 1 mini-terminal block for Output relay |
|
Communication
Slot |
1
slot for Network-M2, Network-MS, ModBus-MS or Relay-MS
cards |
|
Environmental
& Standards |
|
|
Audible
Noise |
<46dB |
|
Operating
Temperature |
0
to 40°C continuous |
|
Safety
markings |
IEC/EN
62040-1 |
|
EMC
Markings |
IEC/EN
62040 -2 |
|
Approvals |
CE
/CB report (TUV) / EAC /
RCM |